The Yokogawa SDV531-S23, also cataloged as the SDV531-S23 Functional Safety Digital Output Module, provides eight isolated 24 V DC discrete output channels for safety logic execution in Yokogawa ProSafe-RS Safety Instrumented Systems.
| Parameter | Specification |
|---|---|
| Model | SDV531-S23 |
| Brand | Yokogawa |
| Module Type | Functional Safety Digital Output Module |
| System Platform | ProSafe-RS; integrated CENTUM VP / CS 3000 networks |
| Number of Channels | 8 isolated channels |
| Output Type | Current source, 24 V DC |
| Rated Output Voltage | 24 V DC (+20% / -10%) |
| Maximum Load Current | 0.6 A per channel; 4.8 A total maximum |
| Minimum Load Current | 35 mA |
| OFF-State Leakage Current | <= 1.6 mA |
| Voltage Drop | <= 1.0 V DC |
| Response Time | <= 30 ms |
| Power Consumption | <= 280 mA at 5 V DC; <= 140 mA at 24 V DC |
| Withstanding Voltage | 2,000 V AC for 1 minute between output lines and system |
| Insulation Resistance | 100 Mohm minimum at 500 V DC |
| Safety Certification | SIL3, IEC 61508 |
| Operating Temperature | -10 deg C to +60 deg C |
The SDV531-S23 provides isolated output channels between the system side and external field circuits. The isolation is specified for protection against external voltage disturbances, ground-loop effects, and electrical noise. The output stage supplies 24 V DC current-source signals for field devices such as actuators, solenoids, relays, contactors, and indicator circuits.
Integrated field diagnostics monitor output-loop conditions. The supplied specifications identify detection of open circuits, short circuits, and field-loop anomalies. The specified maximum load is 0.6 A per channel, with a total maximum load of 4.8 A.
The output electrical interface has a specified voltage drop of no more than 1.0 V DC and an OFF-state leakage current of no more than 1.6 mA. The specified response time is no more than 30 ms.
Q: How many discrete output channels are provided?
A: The SDV531-S23 provides 8 isolated digital output channels.
Q: What output voltage and load current are specified?
A: The rated output is 24 V DC with a tolerance of +20% / -10%. The maximum load is 0.6 A per channel and 4.8 A for all channels combined.
Q: Is the module suitable for SIL3 applications?
A: Yes. The supplied data specifies SIL3 certification according to IEC 61508 for use within ProSafe-RS safety systems.
At PLC DCS Pro Ltd., we are committed to ensuring the quality of our products. Our one-year warranty provides coverage for any defects in material or workmanship, excluding damages caused by deliberate misuse.
This warranty encompasses all instances of product malfunction or failure due to inherent manufacturing flaws, with the exception of intentional damage.
To avail of warranty services, please notify us of any quality-related issues within the warranty period. We may conduct online troubleshooting and examination as needed.
We understand the importance of prompt service. Therefore, we cover return shipping costs for warranty-related returns within the first month of supply. Within three months of supply, we cover one-way shipping costs for warranty-related returns. After three months, the customer is responsible for shipping costs both ways.

Efficient delivery tailored to urgent requirements.
A broad array of stock guarantees prompt availability.
Assuring authenticity and excellence in PLC & DCS parts.
Providing reliable support to clients worldwide.