Sale
100% Original and Authentic
100% Brand New, Ready to ship
Support Refund, 7X24h Service
The Yokogawa ADV151-E00 S2, also cataloged as the ADV151 Digital Input Module, operates as a dedicated hardware component for 24 V DC discrete signal acquisition within Yokogawa CENTUM VP and CENTUM CS 3000 Field Enclosure I/O (FIO) systems.
| Parameter | Specification |
|---|---|
| Model | ADV151-E00 S2 |
| Brand | Yokogawa |
| Origin | Japan |
| Product Type | 32-Channel Digital Input Module |
| Signal Type | 24 V DC sink/source digital input |
| Number of Channels | 32 channels |
| System Compatibility | CENTUM VP, CENTUM CS 3000 DCS with FIO architecture |
| Input ON Voltage | 18.0 to 26.4 V DC |
| Input OFF Voltage | <= 5.0 V DC |
| Maximum Allowable Voltage | 30.0 V DC |
| Input Current | 4.1 mA +/- 20% per channel at rated voltage |
| Input Response Time | <= 8 ms for status input |
| Minimum ON Detection Time | 20 ms for pushbutton input |
| Maximum ON/OFF Cycle | 25 Hz for pushbutton input |
| Internal Current Consumption | Max. 500 mA at 5 V DC |
| Common Layout | 16 channels per common group |
| Redundancy | Supports dual-redundant configuration |
| Dimensions | 5.0 in x 1.0 in x 5.0 in (12.7 cm x 2.5 cm x 12.7 cm) |
| Weight | 0.3 kg |
| Power Consumption | Max. 500 mA at 5 V DC |
The ADV151-E00 S2 is configured for discrete field signal acquisition rather than analog measurement loops. The module accepts 24 V DC ON/OFF states from external devices including pushbuttons, selector switches, limit switches, and relay contacts. Electrical isolation is provided between field inputs and the internal control processing path, allowing the acquired status data to be transferred through the CENTUM FIO system bus.
The module processes input state detection and pushbutton edge counting functions. Each input channel operates within the defined voltage detection range and transfers logic information to the DCS controller through the Yokogawa I/O architecture.
Q: Does the ADV151-E00 S2 support hot-swapping during system operation?
A: The supplied technical data does not specify hot-swap capability. Installation and replacement procedures should follow the Yokogawa CENTUM FIO hardware maintenance instructions.
Q: What is the maximum internal current consumption of the module?
A: The module requires a maximum internal current consumption of 500 mA at 5 V DC.
Q: Can the module operate in a redundant configuration?
A: The supplied specifications indicate support for dual-redundant configuration within compatible Yokogawa DCS architectures.
At PLC DCS Pro Ltd., we are committed to ensuring the quality of our products. Our one-year warranty provides coverage for any defects in material or workmanship, excluding damages caused by deliberate misuse.
This warranty encompasses all instances of product malfunction or failure due to inherent manufacturing flaws, with the exception of intentional damage.
To avail of warranty services, please notify us of any quality-related issues within the warranty period. We may conduct online troubleshooting and examination as needed.
We understand the importance of prompt service. Therefore, we cover return shipping costs for warranty-related returns within the first month of supply. Within three months of supply, we cover one-way shipping costs for warranty-related returns. After three months, the customer is responsible for shipping costs both ways.

Efficient delivery tailored to urgent requirements.
A broad array of stock guarantees prompt availability.
Assuring authenticity and excellence in PLC & DCS parts.
Providing reliable support to clients worldwide.