{"product_id":"ac-800f-power-supply-sa811f-abb-115-230vac-module","title":"AC 800F Power Supply SA811F ABB 115-230VAC Module","description":"\u003ch3\u003eProduct Overview\u003c\/h3\u003e\n\u003cp\u003eThe ABB SA811F (3BDH000013R1) is a power supply module for the AC 800F \/ Freelance controller family. It accepts 115–230 V AC input and delivers regulated 3.3 V and 5 V DC rails for PM802F and PM803F CPU modules.\u003c\/p\u003e\n\u003ch3\u003eCore Specs\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eInput voltage: 115–230 V AC (wide range)\u003c\/li\u003e\n\u003cli\u003eOutputs: 3.3 V DC ±3 % at 6.5 A and 5.0 V DC ±3 % at 5.5 A\u003c\/li\u003e\n\u003cli\u003eTotal output power: 35 W\u003c\/li\u003e\n\u003cli\u003ePower-fail hold-up: \u0026gt;20 ms\u003c\/li\u003e\n\u003cli\u003eProtection: Overcurrent, short-circuit proof, voltage monitoring\u003c\/li\u003e\n\u003cli\u003eCompatibility: PM802F \/ PM803F controllers\u003c\/li\u003e\n\u003cli\u003eDimensions: approx. 67 × 155 × 155 mm\u003c\/li\u003e\n\u003cli\u003eWeight: 0.46 kg\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eHighlights\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eWide-range AC input with EMC filtering\u003c\/li\u003e\n\u003cli\u003eDual regulated low-voltage outputs for CPU board\u003c\/li\u003e\n\u003cli\u003eDiagnostic interface and status indication\u003c\/li\u003e\n\u003cli\u003eDesigned for continuous industrial operation in AC 800F systems\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eCommon Questions\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput voltage?\u003c\/strong\u003e 115–230 V AC.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOutputs?\u003c\/strong\u003e 3.3 V \/ 6.5 A and 5 V \/ 5.5 A.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCompatible CPUs?\u003c\/strong\u003e PM802F and PM803F.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eMounting Steps\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003ePower down the AC 800F controller rack.\u003c\/li\u003e\n\u003cli\u003eInsert the SA811F into the designated power supply slot (leftmost P slot).\u003c\/li\u003e\n\u003cli\u003eConnect AC mains using the appropriate TK 807F \/ TK 808F cable.\u003c\/li\u003e\n\u003cli\u003eSecure the module and restore power.\u003c\/li\u003e\n\u003cli\u003eVerify status indicators and controller startup.\u003c\/li\u003e\n\u003c\/ol\u003e\n\u003ch3\u003eBuying Advice\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eConfirm firmware requirement (V7.1SP2a or higher for some configurations).\u003c\/li\u003e\n\u003cli\u003eEssential spare for AC 800F \/ Freelance systems using PM802F\/PM803F.\u003c\/li\u003e\n\u003cli\u003eEnsure proper AC cable and diagnostic connector are available.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":67800382505027,"sku":"SA811F","price":191.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0587\/5810\/3107\/files\/SA811F_3BDH000013R1__3_edef96bb-8790-4fbd-a9ad-0d7b556b9762.jpg?v=1793093623","url":"https:\/\/www.plcdcspro.com\/th\/products\/ac-800f-power-supply-sa811f-abb-115-230vac-module","provider":"PLC DCS Pro Ltd.","version":"1.0","type":"link"}