{"product_id":"con021-916-200-pr6426-000-130-epro-eddy-current-signal-converter-sensor","title":"CON021\/916-200+PR6426\/000-130 Epro Eddy Current Signal Converter Sensor","description":"\u003ch3\u003e\u003cstrong\u003eCON021\/916-200 Eddy Current Signal Converter\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eOverview\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eModel:\u003c\/strong\u003e CON021\/916-200\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eProduct Type:\u003c\/strong\u003e Eddy Current Signal Converter\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDynamic Performance:\u003c\/strong\u003e\n\u003cul\u003e\n\u003cli\u003eFrequency Range (-3 dB): 0 to 20000 Hz\u003c\/li\u003e\n\u003cli\u003eRise Time: \u0026lt;15 µs\u003c\/li\u003e\n\u003cli\u003eDesigned for PR6422, PR6423, PR6424, PR6425, PR6426, PR 6453\u003c\/li\u003e\n\u003cli\u003eExtended range available with CON021\/91x-xxx\u003c\/li\u003e\n\u003cli\u003ePR6425 always requires extended range converter\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eSpecifications\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eSensor Type:\u003c\/strong\u003e PR6426\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMeasuring Range:\u003c\/strong\u003e 20.0 mm (Extended Range)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eLinearity Error:\u003c\/strong\u003e ≤ 2.5%\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003chr\u003e\n\u003ch3\u003e\u003cstrong\u003ePR6426\/000-130 Eddy Current Sensor\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eOverview\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eModel:\u003c\/strong\u003e PR6426\/000-130\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eProduct Type:\u003c\/strong\u003e Eddy Current Sensor\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDynamic Performance:\u003c\/strong\u003e\n\u003cul\u003e\n\u003cli\u003eSensitivity: 2 V\/mm (50.8 mV\/mil), ≤ ±1.5% max\u003c\/li\u003e\n\u003cli\u003eAir Gap (Center): Approx. 5.5 mm (0.22”) Nominal\u003c\/li\u003e\n\u003cli\u003eLong Term Drift: \u0026lt; 0.3%\u003c\/li\u003e\n\u003cli\u003eRange Static: ±4.0 mm (0.157”)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eSpecifications\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eSleeve Thread:\u003c\/strong\u003e No Thread\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eArmored Cable:\u003c\/strong\u003e Without\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTotal Sensor Length (Mounting Plate):\u003c\/strong\u003e 80 mm x 40 mm\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAdaptor Plug:\u003c\/strong\u003e Without\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTotal Cable Length:\u003c\/strong\u003e Options: 0 (4 m), 1 (5 m), 2 (6 m), 3 (8 m), 4 (10 m)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCable End:\u003c\/strong\u003e LEMO\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Emerson","offers":[{"title":"Default Title","offer_id":42045686448195,"sku":"CON021\/916-200+PR6426\/000-130","price":370.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0587\/5810\/3107\/files\/CON021916-200_PR6426000-130_2.jpg?v=1741327229","url":"https:\/\/www.plcdcspro.com\/products\/con021-916-200-pr6426-000-130-epro-eddy-current-signal-converter-sensor","provider":"PLC DCS Pro Ltd.","version":"1.0","type":"link"}